Illustration only, not a photograph of the product.
Step 2 of 4: Surge & conditioning
PG-10 Surge generator, 10 kV
Surge and DC test set, 10 kV and 1,000 J, that breaks down cable faults so they can be pre-located and pinpointed.
- Surge ranges
- 5/10kV
- Surge energy
- 1,000J
- DC test
- 10kV
- Test current
- 10/20mA
Where it fits
The PG-10 is step 2. It prepares the fault for the reflectometer before it and the pinpointer after it.
-
Step 1: Pre-locate
-
Step 2: Condition
You are here- PG-10 Surge generator, 10 kV
- PG-32 Surge generator, 30 kV
-
Step 3: Pinpoint
-
Step 4: Trace route
Overview
The PG-10 is the smaller of the two surge generators, rated up to 10 kV and 1,000 J. It charges a capacitor and discharges it into the faulty cable, so a high-resistance or intermittent fault breaks down: the reflectometer can then pre-locate it and the pinpointer can hear it at the surface.
The surge voltage is adjusted without steps inside a 5 kV and a 10 kV range, and the full 1,000 J is available in both. The set fires one shot at a time or repeats them, and it also runs DC tests up to 10 kV at 10 or 20 mA.
Modes and settings are chosen on a colour touch screen.
Specifications
Values from the product text on the previous website.
Output and methods
| Surge voltage | 5 and 10 kV ranges, continuously variable |
|---|---|
| Surge energy | 1000 J, full energy in each range |
| DC test voltage | Up to 10 kV |
| Test current, DC | 10 / 20 mA |
| Shots | Single or repeated; a set sequence on request |
Indication
| Display | Colour touch screen |
|---|
PG-10 or PG-32?
The two surge generators side by side.
| Specification | PG-10 | PG-32 |
|---|---|---|
| Output voltage | Up to 10 kV, 5 and 10 kV ranges | 0 to 30 kV |
| Surge energy | 1,000 J | 1,800 J |
| DC test voltage | Up to 10 kV | 0 to 30 kV |
| Shots | Single, intervals or a set sequence | Single, or automatic every 5 s |
| Display | Colour LCD touch screen | Pointer voltmeter and LED display |
Choose by the cable voltage and the energy the fault needs. Not sure? Add both to the quote list and say so in your request.
Works with
Through the ARM Filter the PG-10 feeds the TDR-901 for arc reflection, and its discharges are what the AP-01 listens for.
Step 1, pre-locate
ARM Filter
Arc reflection filter
- Method
- Arc reflection (ARM)
- Works with
- TDR-901, PG-32
Price a PG-10 for your network.